230.00 €
230.0
EUR
230.00 €
Οι τιμές δεν περιλαμβάνουν ΦΠΑ
Not Available For Sale
Apparent Power
1 kVA
Real Power
1 kW
Form Factor
Tower
Rated Voltage
208 / 220 / 230 / 240 Vac
Voltage Range
110 ~ 176 Vac (linear derating between 50% and 100% load); 176 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%)
Rated Frequency
50 / 60 Hz
Frequency Range
50 ~ 60 Hz (auto-sensing)
Input Power Factor
≥ 0.95
Total Harmonic Distortion (THDi)
≤ 5%
Output Voltage
208 / 220 / 230 / 240 Vac (settable via LCD)
Voltage Regulation
± 1%
Frequency
45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode)
Output Power Factor
1
Efficiency
Mains: 93.50% | Battery: 90% | ECO: 98.5%
Waveform
Pure Sine
Transfer Time
0 ms (mains→battery); 4 ms (inverter→bypass typical)
Harmonic Distortion (THDv)
≤ 2% (linear load) | ≤ 5% (non-linear load)
Crest Factor
3:1
Parallel Connection
No
Overload Capability
105% ~ 110% for 30 min; 110% ~ 130% for 10 min; 130% ~ 150% for 30 s; > 150% for 500 ms
Display
LCD
Hot - Swappable battery
No
Battery DC Voltage
24 V
Battery Type
Not Included
Battery Number
0
Charging Current
12 A
Typical Recharge Time
Standard model: 90% capacity restored in 3 hours; Long time model: depend on the capacity of battery
Cold Start
Yes
Full Protection
Short-circuit | overload | overtemperature | battery discharge protection | fan testing protection
Dimension, D x W x H (mm)
144x312x216
Net Weight (kg)
4
Operating Temperature
0°C ~ 40°C
Operating Humidity
0 ~ 95% (non-condensing)
Altitude
≤ 1000 m derating 1% for each additional 100 m
IP Rating
IP20
Noise Level at 1 m
≤ 50 dB
Communication Ports
RS232 (standard) | USB, RS485, dry contacts, SNMP (optional)